Skip to content
Study Notes/Electrical Engineering/Philippine Electrical Code

Philippine Electrical Code (PEC)

Wiring methods, grounding, protection, and installation requirements

1. General Requirements

About the PEC

The Philippine Electrical Code is based on the US National Electrical Code (NEC) and sets minimum requirements for safe electrical installations in the Philippines.

Voltage Classifications

  • Low Voltage (LV): Up to 1000V
  • Medium Voltage (MV): 1001V to 69kV
  • High Voltage (HV): Above 69kV

Standard Service Voltages (Philippines):

  • • Single-phase: 230V (phase-to-neutral)
  • • Three-phase: 400V (phase-to-phase)
  • • Frequency: 60 Hz

Working Space Requirements

Voltage (to ground)Min. Clear DistanceMin. Headroom
0-150V900mm (3 ft)2m (6.5 ft)
151-600V900mm (3 ft)2m (6.5 ft)
601-2500V1200mm (4 ft)2.4m (8 ft)

2. Conductor Sizing

Minimum Wire Sizes

  • Branch circuits: Minimum 3.5 mm² (12 AWG)
  • Lighting circuits: Minimum 2.0 mm² (14 AWG)
  • Fixture wires: Minimum 0.75 mm² (18 AWG)
  • Service entrance: Minimum 8.0 mm² (8 AWG)

Conductor Ampacity

Ampacity depends on conductor size, insulation type, and installation conditions.

Size (mm²)AWGTW (60°C)THHN (90°C)
2.01415A25A
3.51220A30A
5.51030A40A
8.0840A55A
14655A75A
22470A95A

Correction Factors

Temperature Correction

If ambient temp > 30°C, reduce ampacity

At 40°C: multiply by 0.82 (TW)

At 40°C: multiply by 0.91 (THHN)

Bundling/Conduit Fill

4-6 conductors: multiply by 0.80

7-9 conductors: multiply by 0.70

10-20 conductors: multiply by 0.50

3. Voltage Drop

PEC Voltage Drop Limits

Voltage drop should not exceed 3% for branch circuits, 5% total for feeder + branch.

Recommended Limits

  • Branch circuit: Maximum 3%
  • Feeder: Maximum 2%
  • Total (Feeder + Branch): Maximum 5%

Voltage Drop Calculation

Single-phase:

VD = 2 × I × L × R / 1000

Three-phase:

VD = √3 × I × L × R / 1000

VD = voltage drop (V), I = current (A), L = length (m), R = resistance (Ω/km)

Percentage Voltage Drop

%VD = (VD / Vsource) × 100%

Ensure %VD ≤ 3% for branch, ≤ 5% total

4. Wiring Methods

Conduit Types

TypeDescriptionApplication
RSC (Rigid Steel)Thick-wall steel, threadedExposed, hazardous locations
IMC (Intermediate)Medium-wall steel, threadedSimilar to RSC, lighter
EMT (Electrical Metallic Tubing)Thin-wall steel, compression fittingsIndoor dry locations
PVC (Rigid Non-metallic)Plastic conduitUnderground, corrosive areas
FMC (Flexible Metal)Interlocked armorFinal connections to equipment

Conduit Fill

Maximum Conduit Fill

  • 1 conductor: 53% of conduit area
  • 2 conductors: 31% of conduit area
  • 3+ conductors: 40% of conduit area

Applies to same size conductors; calculate for mixed sizes

Box Fill

Each conductor counts as volume allowance:

  • • 14 AWG (2.0 mm²): 32.8 cm³
  • • 12 AWG (3.5 mm²): 36.9 cm³
  • • 10 AWG (5.5 mm²): 41.0 cm³

Add allowance for devices, clamps, and equipment grounding

5. Grounding and Bonding

Purpose of Grounding

  • • Limit voltage from lightning/line surges
  • • Stabilize voltage during normal operation
  • • Facilitate overcurrent device operation
  • • Personnel and equipment safety

Grounding Terminology

Grounded Conductor

Current-carrying conductor intentionally grounded (neutral)

Color: White or gray

Grounding Conductor

Non-current-carrying conductor for fault current

Color: Green or bare

Grounding Electrode System

Types of Grounding Electrodes:

  • Ground Rod: Min. 16mm dia, 2.4m long (copper-clad steel)
  • Ground Plate: Min. 900 cm², 1.5mm thick (copper)
  • Concrete-Encased (Ufer): 6m of #4 AWG in foundation
  • Water Pipe: 3m in contact with earth (if metal)

Ground Resistance

Maximum Ground Resistance

  • Single electrode: ≤ 25 ohms
  • If > 25 ohms: Add supplemental electrode
  • Substations/Industrial: ≤ 5 ohms recommended
  • Communications: ≤ 5 ohms recommended

Equipment Grounding Conductor (EGC)

OCPD Rating (A)Copper EGC (mm²)Aluminum EGC (mm²)
15-202.03.5
303.55.5
605.58.0
1008.014
2001422

6. Overcurrent Protection

General Rules

  • Conductor protection: OCPD rating ≤ conductor ampacity
  • Standard ratings: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, 6000 A

Load Calculations

OCPD Rating ≥ 125% × Continuous Load + 100% × Non-continuous Load

Continuous load = operates 3+ hours continuously

Branch Circuit Ratings

Circuit RatingMin. Wire SizeReceptacle RatingTypical Use
15A2.0 mm²15ALighting
20A3.5 mm²15A or 20AGeneral purpose
30A5.5 mm²30AAppliances

Coordination

Protective devices should be coordinated so that the device nearest the fault clears first (selectivity). Typical ratios:

  • • Fuses: 2:1 ratio between upstream and downstream
  • • Breakers: Follow manufacturer coordination tables

7. Motor Installations

Motor Circuit Components

  • Branch circuit conductors: ≥ 125% of motor FLC
  • Short-circuit protection: Varies by motor type
  • Overload protection: Based on service factor or temp rise
  • Disconnecting means: Required within sight of motor

Motor Branch Circuit Protection

Maximum OCPD Rating (Percent of FLC)

Motor TypeInverse-Time BreakerFuse (Time-Delay)Inst. Trip Breaker
AC Squirrel Cage250%175%1100%
AC Wound Rotor150%150%800%
DC Motor150%150%250%

Motor Overload Protection

  • Service Factor ≥ 1.15: Overload trip ≤ 125% × FLC
  • Temperature Rise ≤ 40°C: Overload trip ≤ 125% × FLC
  • All other motors: Overload trip ≤ 115% × FLC

Multiple Motors

Feeder to multiple motors:

Conductor = 125% × Largest FLC + Sum of other FLCs

OCPD = Largest motor OCPD + Sum of other FLCs

8. Special Installations

Transformer Installation

Primary Protection (Overcurrent)

  • Impedance ≤ 6%: Max 125% of primary current (use next size up)
  • Impedance > 6% to 10%: Max 167% of primary current
  • Secondary protection: Required if primary > 125%

Emergency Systems

  • • Transfer within 10 seconds of power failure
  • • Separate wiring from normal circuits
  • • Circuit breakers must be labeled/identified
  • • Battery backup or generator required

GFCI Requirements

Ground-Fault Circuit Interrupter (5mA trip) required for:

  • • Bathrooms - all receptacles
  • • Kitchens - within 1.8m of sink
  • • Garages and accessory buildings
  • • Outdoors - all receptacles
  • • Laundry areas
  • • Unfinished basements
  • • Swimming pool areas

Hazardous Locations

Class I (Flammable Gases/Vapors)

Division 1: Normal operation

Division 2: Abnormal conditions only

Class II (Combustible Dust)

Division 1: Normal operation

Division 2: Abnormal conditions only

Require explosion-proof or intrinsically safe equipment

Solar PV Systems

  • • Inverter output: Standard AC requirements
  • • DC circuits: Sized for 125% of Isc
  • • Rapid shutdown required for rooftop systems
  • • Disconnect required on both DC and AC sides
  • • Ground-fault protection for systems > 50V

Key Takeaways for EE Board Exam

Must-Know Values

  • ✓ Min. branch circuit: 3.5 mm² (12 AWG)
  • ✓ VD: 3% branch, 5% total
  • ✓ Conduit fill: 40% for 3+ conductors
  • ✓ Ground resistance: ≤ 25Ω single rod
  • ✓ Continuous load: 125%
  • ✓ Motor conductor: 125% FLC
  • ✓ Induction motor OCPD: 250% max

Critical Rules

  • ✓ Grounded = White/Gray (neutral)
  • ✓ Grounding = Green/Bare (safety)
  • ✓ GFCI trips at 5mA
  • ✓ Working space: min 900mm front
  • ✓ Transformer primary: max 125%
  • ✓ Emergency: 10 sec transfer
  • ✓ Service voltage: 230V 1φ, 400V 3φ